    Addressable Systems  
Icon
 
Detectors
 

Addressable Photoelectric Smoke Detectors
 
  Addressable Devices
 
  General
The SD355(A) and SD355T(A) addressable, low-profile plugin photoelectric detectors use a state-of-the-art photoelectric sensing chamber with communications to provide open area protection and are used exclusively with Fire•Lite’s Addressable Fire Alarm Control Panels (FACPs). The SD355T(A) adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help emergency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (P/N RA100Z(A)). The SD355R is a remote test capable detector for use with D355PL or DNR(W) duct smoke detector housings.
spacer
  Features
SLC loop:
» Two-wire loop connection.
» Unit uses base for wiring.
Addressing:
»
Addressable by device.
» Direct Decade entry of address: 01 – 99 with MS-9200 series, and 01 – 159 with MS-9600 series.
Architecture:
» Unique single-source, dual-chamber design to respond quickly and dependably to a broad range of fires.
» Sleek, low-profile design.
» Integral communications and built-in type identification.
» Built-in tamper-resistant feature.
» Removable cover and insect-resistant screen for simple field cleaning.
Operation:
» Withstands air velocities up to 4,000 feet-per-minute (20 m/ sec.) without triggering a false alarm.
» Factory preset at 1.5% nominal sensitivity for panel alarm threshold level.
» Visible LED “blinks” when the unit is addressed (communicating with the fire panel) and latches on in alarm.
Mechanicals:
» Sealed against back pressure.
» Direct surface mounting or electrical box mounting.
» Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box, or 4.0" (10.16 cm) square electrical box (using a plaster ring — included).
Other system features:
» Fully coated circuit boards and superior RF/transient protection.
» 94-V0 plastic flammability rating.
» Low standby current.
Options:
» Remote LED output connection (P/N RA100Z).
 
* Click here more Information  
 
^ Top
 

Intelligent Addressable Ionization Smoke Detectors
 
Addressable Devices
 General
The CP355(A) addressable, low-profile, plug-in ionization detector uses a state-of-the-art ionization sensing chamber to provide open-area protection and is used exclusively with Fire•Lite’s addressable Fire Alarm Control Panels (FACPs). The ionization detector is used to sense products-of-combustion and report the measured level of such products to the fire alarm control panel. Since this detector is addressable, it will help emergency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (P/N RA400Z).
Features
SLC loop:
» Two-wire loop connection.
» Unit uses base for wiring.
Addressing:
» Addressable by device.
» Direct Decade entry of address: 01 – 99 with MS-9200, MS- 9200UD and MS-9200UDLS and 01 – 159 with MS-9600and MS-9600UDLS.
Architecture:
» Unique single-source, dual-chamber design to respond quickly and dependably to a broad range of fires.
» Sleek, low-profile design.
» Integral communications and built-in type identification.
» Built-in tamper-resistant feature.
» Removable cover and insect-resistant screen for simple field cleaning.
Operation:
» Withstands air velocities up to 1,200 feet-per-minute (6.1 m/ sec.) without triggering a false alarm.
» Factory preset at 1.5% nominal sensitivity for panel alarm threshold level.
» Visible LED “blinks” when the unit is addressed (communicating with the fire panel) and latches on in alarm.
Mechanicals:
» Sealed against back pressure.
» Direct surface mounting or electrical box mounting.
» Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box, or 4.0" (10.16 cm) square electrical box (using a plaster ring).
 
* Click here more Information  
 
^ Top
 

Intelligent Addressable Thermal Detectors
 
Addressable Devices
General
The Fire•Lite Alarms H355 Series thermal detectors are addressable sensors that use a state-of-the-art thermistor sensing circuit for fast response. These sensors are designed
to provide open-area protection and are intended for use with the Fire•Lite’s addresable Fire Alarm Control Panels (FACPs). The H355(A) and H355R(A) sensors provide fixed temperature alarm detection at 135°F (57°C). The H355R(A) sensor also responds to rate-of-rise conditions of greater than 15°F (8.3°C) per minute. The H355HT(A) is a fixed high-temperature detector that activates at 190°F (88°C). These thermal detectors provide cost effective, addressable property protection in a variety of applications. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (P/N RA400Z).
 Features
SLC loop:
» Two-wire SLC loop connection.
» Unit uses base for wiring.
Addressing:
» Addressable by device.
» Direct Decade entry of address: 01 – 159 with MS-9600, 01 – 99 with MS-9200UD.
Architecture:
» Sleek, low-profile, stylish design.
» State-of-the-art thermistor technology for fast response.
» Integral communications and built-in device-type identification.
» Built-in tamper resistant feature.
» Built-in functional test switch activated by external magnet.
Operation:
» Factory preset at 135°F (57°C) for the H355(A) and H355R(A); 190°F (88°C) for the H355HT(A).
» Rate-of-rise triggers at 15°F (8.3°C) per minute for the H355R(A).
» 360°-field viewing angle of the visual alarm indicators (two bicolor LEDs). LEDs blink green in Normal condition and turn on steady red in Alarm.
» Visible LEDs “blink” every time the unit is addressed.
Mechanicals:
» Sealed against back pressure.
» SEMS screws for wiring of the separate base.
» Designed for direct-surface or electrical-box mounting.
» Plugs into separate base for ease of installation and maintenance.
» Separate base allows interchange of photoelectric, ionization and thermal sensors.
Other system features:
» Remote test feature from the panel.
» Walk test with address display.
» Low standby current.
» 94-5V plastic flammability rating.
Options:
» Remote LED output connection to optional RA400Z remote LED annunciator.
» Recessed (RMK400) or surface (SMK400E) base mounting kits.
 
* Click here more Information  